CP33 SETTING
THE INJECTION CONTROL PANEL
- Locate the inlet gate valve (B), outlet gate valve (C), needle valve and control valve (A) in the installation diagram.
- Connect water inlet hose at valve (B) to the desired side of your flow meter.
- With your system water flow at its maximum, valve (A) is fully open.
- Slowly close valve (A) until float is positioned just above your desired injection setting. Note: Bounce of the float is a normal condition, the meter setting is read at the high point of the bounce.
- If the inlet hose is connected to the low volume (ounces per
hour) side of the meter, use the needle valve to move the float
to the exact setting you want. Residential pools use this side.
- If the inlet hose is connected to the high volume (gallons per hour) side of the meter, use the inlet control valve (B) to move the float to the exact setting you want.
Remember, the pressure fluctuations will cause the float to bounce and the position of the top of the float at the highest point of the bounce is the flow rate the meter will achieve.

The needle valve (not shown in diagram above) is located on the lower right hand side of the meter and is controlled by a small metal knob.
All valves open when turned counter clockwise and close in a clockwise direction. The outlet gate valve (C) remains open during operation.
See CP33 installation diagram page for more detal.
Note: Over tightening -closing- the needle valve will cause damage to the needle and seat.
For a printable version of the diagram...click here